Four-Way Ceiling Cassette System Engineering Manual
GENERAL DATA / SPECIFICATIONS
Type Single Zone Four-Way Ceiling Cassette
System (Model) (Indoor Unit / Outdoor Unit)
LC187HV
(LCN187HV /
LUU187HV)
LC247HV
(LCN247HV /
LUU247HV)
LC367HV
(LCN367HV /
LUU367HV)
LC427HV
(LCN427HV /
LUU427HV)
Ceiling Grille Model Number (Sold Separately)
PT-UMC1B / PT-UMC1 PT-UMC1B / PT-UMC1 PT-UMC1B / PT-UMC1 PT-UMC1B / PT-UMC1
Cooling Capacity (Min/Rated/Max) (Btu/h)
9,500~18,000~19,800 9,700~24,000~26,700 14,000~36,000~42,000 17,100~42,000~47,100
Cooling Power Input
1
(kW)
1.26 1.91 2.97 4.07
EER (OD 95°F)
15 12.6 13.5 10.3
SEER
20.0 17.0 19.0 17.0
Heating Capacity (Min/Rated/Max) (Btu/h)
9,300~20,000~22,000 10,900~27,000~30,000 14,500~40,000~45,000 17,100~47,000~52,600
Heating Power Input
1
(kW)
1.5 2.60 3.20 4.05
COP (OD 47°F)
- - - -
HSPF
10.1 9.7 9.5 8.6
Power Supply V, Ø, Hz
2
208-230 / 1 / 60
Outdoor Unit Operating Range
Cooling (°F DB)
5-118
Heating (°F WB)
0-64
Indoor Unit Operating Range
Cooling (°F WB)
57-77
Heating (°F DB)
59-81
Indoor Temperature Setting Range
Cooling (°F DB)
65-86
Heating (°F WB)
61-86
Unit Data
Refrigerant Type
3
R410A
Refrigerant Control
EEV
Indoor Unit Sound Pressure Level ±3 dB(A) (H/M/L)
4
38 / 36 / 34 46 / 44 / 43
Outdoor Unit Sound Pressure Level ±3 dB(A)
(Cool/Heat)
4
48 / 52 52 / 54
Indoor Unit Net / Shipping Weight (lbs.)
46 / 55 55 / 65
Outdoor Unit Net / Shipping Weight (lbs.)
133 / 148 203 / 227
Grille Net / Shipping Weight (lbs.)
11 / 20
Power Wiring / Communications Cable (No. x AWG)
2
4 x 18
Compressor (Type x Qty.)
Twin Rotary x 1
Dehumidification Rate (pts./hr.)
5.1 7.7
Fan
Indoor Unit Type x Qty.
Turbo x 1
Outdoor Unit Type x Qty.
Propeller x 1 Propeller x 2
Motor / Drive
Brushless Digitally Controller / Direct
Airflow Rate
Indoor Unit (Max. / H / M / L [CFM])
565/494/424 600/530/459 1,060/989/918 1,060/989/918
Outdoor Unit (CFM)
2,048 2,048 1,942 x 2 1,942 x 2
Piping
Liquid (in.)
3/8
Vapor (in.)
5/8
Indoor Unit Condensate Drain O.D. / I.D. (in.)
1-1/4 / 1
Additional Refrigerant Charge (oz./ft.)
0.43
Maximum Pipe Length (ft.)
164 246
Piping Length
5
(no additional refrigerant, ft.)
25
Maximum Elevation Difference (ft.)
98
Table 3: Four-Way Ceiling Cassette System General Data, continued.
EEV: Electronic Expansion Valve, IDU: Indoor Unit, ODU: Outdoor Unit. This unit comes with a dry
helium charge.
This data is rated 0 ft above sea level, with 24.6 ft of refrigerant line per indoor unit and a 0 ft level
difference between outdoor and indoor units.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb
(WB); and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet bulb
(WB); and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1
Power Input is rated at high speed.
2
All power wiring/communication cables from ODU to IDU are field supplied and are to be minimum 18
AWG, 4-conductor, stranded, shielded or unshielded (if shielded, must be grounded to chassis at ODU
only), and must comply with applicable local and national codes.
3
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy
R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of
CAA.
4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and are the
same in both cooling and heating mode. These values can increase due to ambient conditions during
operation.
5
Piping lengths are equivalent.