Problem solving
65
Greentherm T9800 SE 160/199 – 6 720 816 815 (2022/01)
AA
3)
Condensing unit flue gases temperature [16]
above 392 °F (200 °C) and/or flue gases
temperature [15] above 145 °F(63 °C) at the
exhaust sensor [15]. Appliance regulates power to
protect against overheating.
▶ Check flue gas temperature sensor.
1)
▶ Check water inlet temperature sensor.
1)
▶ Descale appliance ( section 7.3).
1)
AD Flue blockage detected during startup due to
insufficient combustion air. Appliance power
derate and possible reduction of comfort level.
▶ Reset error (press and hold on/off button for 3
seconds).
If the problem persists:
▶ Check air openings and exhaust opening for
obstructions and reset the error.
▶ Check if flue length is according to specification
(section 4.6) and reset the error.
▶ Check if the air filter is dirty or clogged, replace it if
needed.
▶ Perform gas and air tuning ( section 8.11).
1)
BB Fan calibration triggered due to missed ignitions. ▶ Check gas inlet pressure ( section 4.13).
1)
▶ Perform gas and air tuning ( section 8.11).
1)
BC Successive fan calibration with similar learned
values.
▶ Check gas inlet pressure ( section 4.13).
1)
▶ Perform gas and air tuning ( section 8.11).
1)
C1
4)
C2
4)
Excessive flue blockage detected during startup
due to insufficient combustion air.
Appliance shuts down for safety.
▶ Reset error (touch and hold on/off button for 3
seconds).
If the problem persists:
▶ Check air intake and exhaust pipes and terminals for
obstructions and reset the error.
▶ Check if flue length is according to specification
(section 4.6) and reset the error.
▶ Check if the air filter is dirty or clogged, clean or
replace it if needed.
▶ Perform gas and air tuning ( section 8.11).
1)
C3 Flow sensor [14] does not detect water
recirculation.
▶ Check pump and connections.
1)
▶ Check recirculation circuit for any blockage.
C5 Bypass water valve [8] disconnected or damaged. ▶ Check bypass water valve wire connections.
1)
If the problem persists:
▶ Replace the bypass water valve and/or wire
connections. After valve replacement, proceed with
bypass water valve calibration (section 6.7).
1)
C7 Fan [2] disconnected or damaged. ▶ Check fan wire connections.
▶ Reset error (touch and hold on/off button for 3
seconds)
If the problem persists:
▶ Replace the fan and/or wire connections.
1)
C8 Main water valve [22] disconnected or damaged. ▶ Check main water valve wire connections.
1)
▶ Proceed with main water valve calibration.
If the problem persists:
▶ Replace main water valve and/or wire connections.
After valve replacement, proceed with main water
valve calibration (section 6.7).
1)