Operating Instructions
Greentherm T9800 SE 160/199 – 6 720 816 815 (2022/01)
52
▶Touch the symbol .
Display shows following menu.
Off
–On
The current selection is in green color.
Touch symbols or to select the desired option.
▶Touch the symbol .
Touch the symbol to return to main menu.
PE Appliance Type
This menu shows the technical specifications of the appliance.
AP Appliance Power
ML Model
TP Type
AP Appliance Power
▶Touch the symbol .
Display shows appliance power (default set).
199K BTU
or
160K BTU
Touch the symbol to exit.
Touch symbols or to scroll through other menus.
ML Model
▶Touch the symbol .
Display shows appliance model.
Indoor
Touch the symbol to exit.
Touch symbols or to scroll through other menus.
TP Type
▶Touch the symbol .
Display shows appliance model.
Residential
Touch the symbol to exit.
AB Region Selection
▶Touch the symbol .
Display shows following menu.
Europe
North America
A4 Demonstration
Simulates in the display, the appliance is functioning.
(Only available when burner is not working)
6.7 Water valves calibration
Water valve calibration must be done when main water valve or
bypass valve is replaced. Also required when electronic control
unit is replaced.
The water valve calibration process takes several minutes.
Do not interfere with the appliance.
Only possible after access Technical Settings menu ( section
6.6).
6.7.1 MF main-water valve auto calibration
▶Open one hot water faucet.
Before moving to the next step,
Make sure there is water flow.
Access menu PA.
Touch symbol OK.
Touch symbols or to select MF main valve.
Touch symbol OK.
The appliance will start the auto calibration of main valve.
Water flow will shut-off.
Wait until indication of calibration completed appears on
the screen.
Touch the symbol to return to main menu.
6.7.2 BP bypass valve auto calibration
▶Open one hot water faucet.
Flow rate between 0.80 GPM and 1.80 GPM is required.
It's possible to confirm this value by entering BP bypass-
water valve menu.
Access menu PA.
Touch symbol OK.
Touch symbols or to select BP bypass-water
valve.