Electrical Installation Tester
Measur ements
49
To measure RCD tripping current:
1. Turn the rotary dial to the I
∆N
position. See Table 17.
Table 17. RCD Tripping Current/Dial and Terminal Settings
F1
F3
F4
hwl009.eps
Push
Button
Action
1664 FC
1663
1662
Select RCD test polarity: 0° or 180°
• • •
Select RCD
• • •
RCD current setting: 10 mA, 30 mA, 100 mA, 300 mA, 500
mA, 1000 mA, or Var
• • •
Start the selected test
• • •
2. Press to select the RCD current rating (10, 30, 100, 300, 500,
1000 mA). If the RCD has a special nominal current setting other than the
standard options, you can use a custom setting with the Var mode.