Installation Procedure
Installation Procedure
Model Outdoor unit Input Current[A] Power supply
Outdoor unit Indoor unit
Rated Voltage Range Outdoor (Down_Amp)
Indoor Total MCA MFA
Hz Volts Min. Max. Cooling
AC030BXPDKC
AC030BNPDKC 50/60 220 ~ 240 198 264 20 2.0 22.0 22.0 25.0
AC036BXPDKC
AC036BNPDKC 50/60 220 ~ 240 198 264 24 2.0 26.0 26.0 30.0
AC048BXPDKC
AC048BNPDKC 50/60 220 ~ 240 198 264 32 2.0 34.0 34.0 40.0
AC048BXPDNC
AC048BNPDKC 50/60 380 ~ 415 342 457 12 2.0 14.0 14.0 15.0
AC054BXPDNC
AC054BNPDKC 50/60 380 ~ 415 342 457 12 2.0 14.0 14.0 15.0
NOTE
1 Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed
range limits
2 Maximum allowable voltage variation between phases is 2%.
3 Wire size & type must comply with the applicable local and national code.
Wire size: Based on the value of MCA.
Wire type: 60245 IEC57(IEC) or H05RN-F(CENELEC) grade or more.
4 MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
5 MCA represents maximum input current.
MFA represents capacity which may accept MCA
Abbreviations
MCA: Min. Circuit Amps. (A)
MFA: Max. Fuse Amps. (A)
Step 10 Optional: Extending the power
cable
1 Prepare the following tools.
Tools Spec Shape
Crimping pliers MH-14
Connection sleeve
(mm)
20 x Ø6.5 (H x OD)
Insulation tape Width 19 mm
Contraction tube
(mm)
70 x Ø8.0 (L x OD)
2 As shown in the figure, peel off the shields from the
rubber and wire of the power cable.
Peel off 20 mm of cable shields from the pre-
installed tube.
Power cable
(Unit: mm)
20
20
20
60
120
180
180
120
60
20
20
20
Pre-installed
tube for the
power cable
DB68-11731A-02_IBIM_PAC Mirage Cooling Only_TC_EN_.indd 44DB68-11731A-02_IBIM_PAC Mirage Cooling Only_TC_EN_.indd 44 2023-07-19 오전 9:52:182023-07-19 오전 9:52:18