32
English
Installation Procedure
Installation Procedure
Installation Procedure
Installation Procedure
Step 1 Choosing the installation location
Determine the installation location considering the following
conditions and obtain the user approval.
Indoor unit
Install the unit where the pipes and cables can be easily
connected to the outdoor unit.
Install the unit where there are no obstacles against
the wind around the air intake and air outlet.
Install the unit on a flat and stable surface that
can hold the unit’s weight. Otherwise, the unit may
generate noise and vibrations.
Do not install the unit near highly frequented doors and
passages.
Do not install the unit in a location exposed to direct
sunlight.
Top view Side view
More than 60cm
<Wall installation>
<Corner installation>
More than 100cm
More than 50cm
Air outlet
Air intake
Outdoor unit
Install the unit where it will not experience oil
leakages, salt collection, gas exposure, or sulfide gas
risk, and keep it and safe from other dangers.
Install the unit where does not disturb your neighbors as
they may be affected by the noise or airflow coming from
the unit.
Install the unit where no rainwater can collect on or near it.
Install the unit in a well-ventilated location away from
direct sunlight or strong winds.
Install the unit where the pipes and cables can be easily
connected to the indoor unit.
Maintain sufficient space for repairs and service.
Make sure that condensed water dripping from the
drain hose is directed away safely.
If there is any unavoidable reason to install the unit at
such a place, take the following measures:
When installing the unit at a roadside concentrated
with buildings, install it parallel to the road.
Install the unit so that the air outlet faces the wall
such as rooftop that may be subjected to strong wind.
Strong wind
Rooftop
When installing the outdoor unit near the seashore, make sure
that it is not directly exposed to sea breeze. If you cannot find
an adequate place, a protection wall should be constructed.
Install the outdoor unit at a place (such as near a
building) where it can be protected from sea breeze.
Failure to do so may cause damage to the outdoor unit.
Outdoor Unit
Sea breeze
Sea
Outdoor Unit
Sea breeze
Sea
If you cannot avoid a place near the seashore, construct
a protection wall around the outdoor unit.
Sea
Sea breeze
Outdoor Unit
Protection wall
Construct a protection wall made of solid material such
as concrete to block sea breeze. Make sure that its
height and width are 1.5 times greater than the size of
the outdoor unit. In addition, secure a space larger than
600 mm between the protection wall and the outdoor
unit for exhausted air to ventilate.
Install the unit at a place where water can drain smoothly.
If you have any difficulty in finding an installation
location, contact your manufacturer.
Be sure to clean sea water and dust on the heat
exchanger of the outdoor unit and apply a corrosion
inhibitor on it (at least once in a year).
DB68-11731A-02_IBIM_PAC Mirage Cooling Only_TC_EN_.indd 32DB68-11731A-02_IBIM_PAC Mirage Cooling Only_TC_EN_.indd 32 2023-07-19 오전 9:52:142023-07-19 오전 9:52:14
Loading ...
Loading ...
Loading ...