Cleaning at a Glance
Cleaning and Maintenance
Periodical maintenance
Unit Maintenance item Interval
Requires qualified
technicians
Indoor unit
Clean the air filter. Once every 2 weeks
Clean the condensate drain pan. Once a year Required
Clean up the heat exchange. Once a year Required
Clean the condensate drain pipe. Once every 4 months Required
Replace the remote control Batteries. Once a year
Outdoor unit
Clean the heat exchanger on the outside of the unit.
Once every 4 months Required
Clean the heat exchanger on the inside of the unit.
Once a year Required
Clean the electric components with jets of air. Once a year Required
Verify that all the electric components are firmly
tightened.
Once a year Required
Clean the fan. Once a year Required
Verify that the fan assemblies are firmly
tightened.
Once a year Required
Clean the condensate drain pan. Once a year Required
CAUTION
• Be sure to perform the maintenance check periodically. This work improves the air conditioner's
efficiency.
• The frequency of maintenance work may vary depending on the geographical area, amount of dust,
and other environmental elements. If the air conditioner is installed in a very dusty place, perform the
maintenance work more frequently.
• Make sure that the maintenance work must be done by qualified technicians. For more detailed
information, refer to the Installation manual.