Installation Procedure
Installation Procedure
NOTE
Be sure to insulate the pipes without gaps or cracks,
and use adhesive between the connecting parts of the
insulation to prevent moisture from entering.
When bending the pipe, try to secure a large bending
radius (over 100 mm) to prevent the copper pipe from
distorting.
Make sure that the thickness of the insulation does not
get thinner on the pipe’s bending area.
When the insulation thickness becomes thinner, use
extra insulation to maintain thickness.
When installing the pipe hanger, use extra PE- foam
insulation (over 5 mm) to make the width of the
insulation 3 times wider than the hanger. Do not use
cable ties as a pipe hanger.
Step 6 Purging inert gas from the
indoor unit
The indoor unit comes with nitrogen gas (inert gas) charged
at the factory. Therefore, all inert gas must be purged before
connecting the assembly piping.
Unscrew the pinch pipe at the end of each refrigerant pipe.
High pressure
pipe
Low
pressure
pipe
NOTE
To prevent dirt or foreign objects from getting into the pipes
during installation, do not remove the pinch pipe completely
until you are ready to connect the piping.
Step 7 Optional: Cutting and flaring
the pipes
1 Make sure that you have the required tools available: pipe
cutter, reamer, flaring tool, and pipe holder.
2 If you wish to shorten the pipes, cut them with a pipe
cutter, ensuring that the cut edge remains at a 90° angle
to the side of the pipe. Refer to the illustrations below for
examples of edges cut correctly and incorrectly.
Pipe cutter
Pipe
90°
Oblique Rough Burr
3 To prevent any gas from leaking out, remove all burrs at
the cut edge of the pipe, using a reamer.
4 Slide a flare nut on to the pipe and modify the flare.
D
A
Flare
90° ±2°
45° ±2°
Pipe
R 0.4 to 0.8 mm
D
L
Flare
Outer Diameter (D) Depth (A) Flare dimension (L)
Ø 6.35 mm 1.3 mm 8.7 to 9.1 mm
Ø 9.52 mm 1.8 mm 12.8 to 13.2 mm
Ø 12.70 mm 2.0 mm 16.2 to 16.6 mm
Ø 15.88 mm 2.2 mm 19.3 to 19.7 mm
Ø 19.05 mm 2.2 mm 23.6 to 24.0 mm
DB68-11731A-02_IBIM_PAC Mirage Cooling Only_TC_EN_.indd 38DB68-11731A-02_IBIM_PAC Mirage Cooling Only_TC_EN_.indd 38 2023-07-19 오전 9:52:162023-07-19 오전 9:52:16