Installation Procedure
7 Setting outdoor unit option switch and address manually
a Setting the option
Press and hold K2 to enter the option setting. (Only
available when the operation is stopped)
If you enter the option setting, display will show
the following.
Seg 1 and Seg 2 will display the number for
selected option.
Seg 3 and Seg 4 will display the number for set
value of the selected option.
If you have entered option setting, you can shortly
press the K1 switch to adjust the value of the Seg 1,
Seg 2 and select the desired option.
Example)
If you have selected desired option, you can shortly
press the K2 switch to adjust the value of the Seg 3,
Seg 4 and change the function for the selected option.
Example)
After selecting the function for options, press and
hold the K2 switch for 2 seconds. Edited value of
the option will be saved when entire segments
blinks and tracking mode begins.
Option
item
Input
u
nit
SEG1 SEG2 SEG3 SEG4 Function
Channel address Main 0 0
A U
Automatic setting
(Factory default)
00~15 Manual setting
Snow
accumulation
prevention
control
Main 0 1
0 0
Disabled (Factory
default)
0 1 Enabled
Step for Silence
mode
Main 0 2
0 0
Disabled (Factory
default)
0 1 Step1
0 2 Step2
0 3 Step3
Option
item
Input
u
nit
SEG1 SEG2 SEG3 SEG4 Function
Type of
Silence mode
Main 0 3
0 0
Aut
omatic Silence
mode (Factory
default)
0 1
Manual Silence
mode
Temperature unit Main 0 4
0 0
Celsius
(default)
0 1 Fah
renheit
Not applicable Main 0 5
0 0 Not applicable
0 1 Not applicable
Current restriction
rate ¹⁾
Main 0 6
0 0
100%
(Factory
default)
0 1 9
5%
0 2 90%
0 3 85%
0 4 80%
0 5 75%
0 6 70%
0 7 65%
0 8 60%
0 9 55%
1 0 50%
1 1 100%
Dedicated mode
for cooling/
heating ²⁾
Main 0 7
0 0
Cooling / Heating
operation (default)
0 1
Cooling operation
only
0 2
Heating operation
only
¹⁾ Current restriction rate : When restriction option is
set, cooling and heating performance may decrease.
²⁾ AC***BXAD*C models are cooling-only models and
do not support heating mode. These models operate
in cooling mode only, even if "heating operation
only" mode is enabled.
CAUTION
Edited option will not be saved if you do not end the
option setting as explained in above instruction.
While you are setting the option, you may press and hold
the K1 button to reset the value to previous setting.
If you want to restore the setting to factory default, press and
hold the K4 button while you are in the option setting mode.
If you press and hold the K4 button, setting will be
restored to factory default but it doesn’t mean that
restored setting is saved. Press and hold the K2
button. When the segments shows that tracking
mode is in progress, setting will be saved.