41
English
Installation Procedure
Step 9 Connecting the power and
communication cables
CAUTION
Always remember to connect the refrigerant pipes
before performing the electric connections.
When disconnecting the system, always disconnect the
e
l
ectric cables before disconnecting the refrigerant
pipes.
Always remember to connect the air conditioner to
the grounding system before performing the electric
connections. Use a crimp ring terminal at the end of
each wire.
Electrical work must be done by the certified personnel.
Wiring work should be performed in compliance with
related regulations following technical specifications
and installation guide.
Be sure to install an exclusive power supply. If you use a
power strip for multiple electrical connections, there is
a risk of electric shock or fire.
Be sure to install a circuit breaker with a rated current
sensitivity of over 30 mA.
Fasten the screws on the terminal block to be within
the rated range and so that they do not loosen.
Be sure to connect the ground wire. Install the power
wire and make sure it is shorter than 50 m. If the length
of the power wire exceeds 50 m, the product may not
work properly or the wire may be damaged.
1 Remove the screw on the electrical component box and
remove the cover plate.
2 Route the cables through the sides or back of the indoor
unit and then connect them to the terminals noting the
figure below.
3 Route the other end of the cable to the outdoor unit
through the ceiling & the hole on the wall.
4 Reassemble the electrical component box cover, carefully
tightening the screw.
AC030/036/048BNPDKC (1-pahse)
Indoor Unit
Outdoor Unit
1(L)
1(L)
2(N)
F1
F2
L N
F1
F2
2(N)
Cable clamp
Communication
F1/F2
DC 12V
V1/V2 Connector
Wi-Fi Kit Connection
Indoor power
cable
Main power
cable
Communication
cable
Cable tie
AC048/054BNPDKC (3-pahse)
Indoor Unit
Outdoor Unit
1(L)
1(L)
F1 F2
2(N)
L1(R)
L2(S)
L
N
F1 F22(N)
Indoor power cable
Main power
cable
Cable tie
Communication
cable
Cable clamp
Communication
F1/F2
DC 12V
V1/V2 Connector
Wi-Fi Kit Connection
NOTE
DC12V Connection for Wi-Fi Kit : Cut the wires of the
V1/V2 connector and then connect the wires to the
Wi-Fi Kit.
DB68-11731A-02_IBIM_PAC Mirage Cooling Only_TC_EN_.indd 41DB68-11731A-02_IBIM_PAC Mirage Cooling Only_TC_EN_.indd 41 2023-07-19 오전 9:52:172023-07-19 오전 9:52:17