Electrical Installation Tester
Specific ations
81
Auto Discharge
Discharge time constant <0.5 second for C = 1 µF
or less.
Live Circuit Detection Inhibits test if terminal voltage >30 V prior to
initiation of test.
Maximum Capacitive Load
Operable with up the 5 µF load.
Insulation Safety Pretest Connections from the Tester to L, N, and PE are
required.
Continuity Testing (R
LO
)
Range
(Autoranging)
Resolution
Open Circuit
Voltage
Accuracy
20 0.01
>4 V
±(1.5 % + 3 digits)
[1]
200 0.1
>4 V
±(1.5 % + 3 digits)
2000 1
>4 V
±(1.5 % + 3 digits)
[1] For 10 mA, add 3 digits.
Note: The number of 250 mA @ 1 continuity tests with a set of new batteries is >1500.
Range Setting Display Range Test Current
[1]
250 mA
0.2 to 2.0
250 mA
2 to 160
250 mA to 50 mA
160 to 800
10 mA
800 to 2000
2 mA
10 mA
0 to 800
10 mA
800 to 2000
2 mA
[1] All test currents ±10 %.
Test Probe Zeroing
Press to zero the test probe.
Can subtract up to 3 of lead resistance.
Error message for >3 .
Live Circuit Detection
Inhibits test if terminal voltage >10 V ac detected prior to
initiation of test.