Electrical Installation Tester
Measur ements
51
6. Press and release . If Auto Start is turned on (Power-on option 'Up'),
the test starts automatically as soon as the mains voltage is detected and
the required test leads are connected.
Wait for the test to complete.
The primary display shows the RCD trip current.
The secondary display shows the fault voltage (voltage drop on PE
wire) related to the rated residual current.
For type A and type AC waveforms, press down to display the trip
time.
If the trip current and the trip time (Type A / AC RCDs only) meets the
appropriate standard of the RCD, RCD shows on the display. For
more information, see the RCD Tripping Time table in the
Specifications section.
To measure RCD tripping current for a custom RCD setting - Var mode, see
page 46.