Electrical Installation Tester
Measur ements
49
To measure RCD tripping current:
1. Turn the rotary dial to the I
N
position. See Table 17.
Table 17. RCD Tripping Current/Dial and Terminal Settings
F1
F3
F4
hwl009.eps
Push
Button
Action
1664 FC
1663
1662
Select RCD test polarity: 0° or 180°
Select RCD
RCD current setting: 10 mA, 30 mA, 100 mA, 300 mA, 500
mA, 1000 mA, or Var
Start the selected test
2. Press to select the RCD current rating (10, 30, 100, 300, 500,
1000 mA). If the RCD has a special nominal current setting other than the
standard options, you can use a custom setting with the Var mode.