Rinnai Tankless Water Heater Installation and Operation Manual 42
2. Non-Direct Vent (Room Air and External)
Room Air and External Termination Clearances
Canadian Installations
1
(CSA B149.1)
U.S. Installations
2
(ANSI Z223.1/NFPA 54)
Ref Description Other than direct vent
(Outdoor unit and/or Room Air)
Other than direct vent
(Outdoor unit and/or Room Air)
A Clearance above grade, veranda, porch, deck, or balcony 12 in. (30 cm) 12 in. (30 cm)
B Clearance to window or door that may be opened 36 in. (91 cm)
4 ft (1.2 m) below or to side of opening; 1 ft
(300 mm) above opening
C Clearance to permanently closed window * *
D Vertical clearance to ventilated so󰀩t, located above the terminal within
a horizontal distance of 2 ft (61 cm) from the center line of the terminal
* *
E Clearance to unventilated so󰀩t * *
F Clearance to outside corner * *
G Clearance to inside corner * 12 in.
H Clearance to each side of center line extended above meter/regulator
assembly
3 ft. (91 cm) within a height 15 ft.
(4.6 m)
*
I Clearance to service regulator vent outlet 3 ft. (91 cm) *
J Clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other appliance
36 in. (91 cm)
4 ft (1.2 m) below or to side of opening; 1 ft
(300 mm) above opening
K Clearance to a mechanical air supply inlet 6 ft (1.83 m)
3 ft (91 cm) above if within 10 ft
(3 m) horizontally
L Clearance above paved sidewalk or paved driveway located on public
property
7 ft (2.13 m) [1]
Vents for Category II and IV appliances
cannot be located above public walkways
or other areas where condensate or vapor
can cause a nuisance or hazard.
M Clearance under veranda, porch, deck, or balcony 12 in. (30 cm) [2] *
Clearance to opposite wall is 24 in. (60 cm).
[1] A vent shall not terminate directly above a sidewalk or paved driveway that is
located between two single family dwellings and serves both dwellings.
[2] Permitted only if veranda, porch, deck, or balcony is fully open on a minimum
of two sides beneath the oor.
[3] If locally adopted installation codes specify clearances di󰀨erent than those
illustrated, then the most stringent clearance shall prevail.
*Clearances are in accordance with local installation codes and the
requirements of the gas supplier. (Dégagement conforme aux codes
d’installation locaux et aux exigences du foumisseur de gaz.)
X
V
SNOW
TERMINATION
Clearance in
Ref. A also
applies to
anticipated
snow line
Regulator vent outlet
AIR SUPPLY INLET
VENT TERMINAL
AREA WHERE TERMINAL
IS NOT PERMITTTED
X
V
SNOW
TERMINATION
Clearance in
Ref. A also
applies to
anticipated
snow line
Figure 38: Room Air and External Termination Clearances
Notes:
1
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
2
In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
Table 17