Rinnai Tankless Water Heater Installation and Operation Manual 38
Concentric Pipe: Installation
Instructions
1. Remove and discard screw from concentric
ue connection.
2. Remove exhaust adapter ring (discard for
concentric venting congurations.)
3. Install the concentric vent. Ensure it is properly
seated.
4. Secure the vent pipe to the concentric ue
connection with the supplied screw.
Concentric
Vent
Mount Concentric Pipe Through Wall
If venting through an exterior wall, align the wall
mounting bracket template (located in literature
bag) to the wall and follow instructions on the
template for appropriate vent hole location. Use
a level to make sure the wall mounting bracket is
even and level.
Wall Mounting
Bracket Template
Level
Wall Mounting
Bracket
Table 13: Concentric Pipe: Vent Applications
Horizontal Wall Terminations
2 in. x 4 in.
3 in. x 5 in.
Vertical Roof
Terminations
2 in. x 4 in.
and
3 in. x 5 in.
Table 14: Concentric Pipe: Maximum Vent Length
Concentric Vent Maximum Equivalent Length
Vent Sizes 2 in. x 4 in. 3 in. x 5 in.
Vent Lengths 65 ft (20 m) 150 ft (46 m)
45° elbow is equivalent to 3 ft (1 m)
90° elbow is equivalent to 6 ft (2 m)
Figure 29
Figure 26
Figure 27
Figure 28
Figure 30
Install the venting termination according to the
diagrams and instructions in this manual. Slope
the venting 1/4 in. per foot toward the appliance
according to the vent manufacturer’s installation
instructions. Dispose of condensate per local
codes.
IMPORTANT