6. Operation and Conguration of
S3M UPS Models and Battery Cabinets
EOD Battery Volt: End of discharge voltage is the low voltage cuto of the batteries during a battery mode operation.
The value can be 1.60~1.90. The default value is 1.67V/cell, or 10.02Vdc per battery.
FloatTempCompenCoe: Modies the voltage of compensation after enabling the switch. The value can be
0.001~0.007V/cell/°C. The default value is 0.003V/cell/°C.
Boost Charge Setting: Boost charge can be set to Disable or Enable. The default value is Enable.
No Battery Warning: Keep this alarm enabled if you want the UPS to provide a warning when no batteries are present.
The default value is Enable.