Tripp Lite BP240V65L-NIB series ±120VDC External Battery Cabinet

Owner's Manual - Page 63

For BP240V65L-NIB. Also, The document are for others Tripp Lite models: BP240V65, BP240V65-NIB, BP240V65L, BP240V100, BP240V100-NIB, BP240V100L, BP240V100L-NIB

PDF File Manual, 208 pages, Read Online | Download pdf file

BP240V65L-NIB photo
Loading ...
Loading ...
Loading ...
63
6. Operation and Conguration of
S3M UPS Models and Battery Cabinets
Step 4: Setting Chg. cur. limiting coef (C)
The charging current limit is a multiple of the battery capacity. It is used to set the battery boost charging time limit. The
value can be 0.05~0.25, and is 0.25 by default. Obtain the Charging (Chg) current (cur) limiting coecient (C) based on
the specic S3M UPS and battery cabinet model combination from the chart in Section 6.4.
Float and Boost Voltage: The UPS is factory-set for proper oat (2.27V/cell, 13.62V/battery) and boost (2.35V/cell,
14.1V/battery) voltages.
Celloatvoltage:The oat voltage value can be 2.23~2.30 V/cell. The default value is 2.27 V/cell.
Cell boost voltage: The battery equalized voltage value can be 2.30~2.40 V/cell. The default value is 2.35 V/cell.
Step 5: Setting Aver Changing Duration (min)
Setting the Average Charging Duration in minutes is an estimation of the boost charger time duration to charge new
batteries to 90% capacity at 25°C. Obtain the recommended Average (Aver) Charging Duration (min) number based on
the specic S3M UPS and battery cabinet model combination from the chart in Section 6.4. Note the recommended
battery boost charge durations are estimates only based on new batteries. These numbers may change with the age
of the batteries and the battery ambient temperature. To change the Aver Charging Duration, press directly on the
defaulted 240 value in the display.
The Average (Aver) charging duration is the battery boost charge time limit. The value can be 1~999 min. The default is
value 240 (4 hours).
Loading ...
Loading ...
Loading ...