62
6. Operation and Conguration of
S3M UPS Models and Battery Cabinets
6.3.4 Conguring the S3M25-100K UPS and Optimizing
Charging of
the BP240V65/V65L and BP240V100/V100L Battery Cabinets
Step 1: Setting the Battery Group
The Battery Group is Quantity 1 for every set of 20 batteries that are in and/or connected to the UPS model. For
example, UPS model S3M100K UPS has no internal batteries and is Battery Group 1 by default. However, to connect a
BP240V100L cabinet with 40 internal batteries to the S3M100K, the S3M100K UPS must be congured to Battery
Group 2. To connect a second BP240V100L cabinet to the S3M100K UPS, the Battery Group must be set to 4 (four
sets of 20 batteries). Obtain the Battery Group number based on the specic S3M UPS and Battery Cabinet models
combination from the chart under Section 6.4.
The value can be 1 to 8. The default value is 1 for S3M UPS models without internal batteries.
Step 2: Setting the Battery Number
The battery number must remain at 20 for all S3M10-100K UPS models when connected to external battery cabinets
designed for the S3M-Series UPS Series.
Step 3: Setting Single Battery (Ah) Capability
Change the Single Battery (Ah) Capability to the individual Ah capacity for one individual battery as follows for the specic
battery cabinet model:
BP240V40/BP240V40L: the Single Battery (Ah) Capacity is 40
BP240V65/BP240V65L: the Single Battery (Ah) Capacity is 65
BP240V100/BP240V100L: the Single Battery (Ah) Capacity is 100
The Single Battery (Ah) values can be 7~2000.
Scroll to the next display screen by pressing the down arrow.