800.558.1711 Installation & Operation Instructions
Recommended HVAC System Installation
DUCTING TO HVAC SYSTEMS
The recommended installation draws air from a dedicated indoor air return and ducts the supply of the
dehumidier to the air supply of the existing HVAC system. Utilize the optional fresh air ventilation duct to
provide outside air.
• Install a dedicated 10" air return for the Dehumidier from a central area of the structure.
• Install an insulated duct from outside to the 6" collar of the Dehumidier to provide fresh air
ventilation (optional).
• Duct the supply of the Dehumidier to the supply of the existing HVAC system with a backdraft damper.
• If the existing system has multiple returns, instead of installing a dedicated return to the
Dehumidier, it is possible to select one to disconnect from the existing HVAC system and use it for the
dedicated Dehumidier return. Select a return from a central location in the house that is always open to
the rest of the structure. DO NOT use a return from a room where doors are kept closed.
• DO NOT locate return in a bathroom or kitchen.
• Control should be located remotely from the dehumidier and placed in a central location.
• Please visit our website at www.Broan-NuTone.com for more installation options.
Santa Fe
Supply
Air Handler
HVAC Supply
Dedicated Ultra-Aire 90 Return to A/C Supply
HVAC Return
Fresh Air Intake
(Optional)
Motorized
Damper
Indoor
Air Return
Backdraft
Damper
Dedicated Return to HVAC Supply
Supply