Installation & Operation Instructions 800.558.1711
Important Precautions
• The device is designed to be installed indoors in a space that is protected from rain and ooding.
• Install the unit with enough space to access one of the side panels for maintenance and service.
• Avoid directing the discharge air at people. The dehumidier should be used in the upright position.
• If used near a water source, be certain there is no chance the unit could fall into the water or get splashed and
that it is plugged into a dedicated circuit and Ground Fault Circuit Interrupter (GFCI) protected outlet.
• DO NOT use the dehumidier as a bench or table.
• DO NOT place the dehumidier directly on structural building members without vibration absorbers or
unwanted noise may result. Place the Dehumidier on supports to raise the base of the unit.
• A drain pan with a oat switch MUST be placed under the dehumidier if installed above a living area or above
an area where water leakage could cause damage.
Location Considerations
• Allow sucient clearance to handle the unit’s overall
dimensions as well as the necessary return and
supply ductwork to the unit.
• Allow sucient clearance for lter removal and to
prevent airow obstruction.
• Electrical service access will require the removal of
a side panel. Allow sucient clearance on a side of
the unit.
• Locate the dehumidier in an area where the cord’s
length (9') easily reaches a 115 VAC electrical outlet
with a minimum of a 15 Amp circuit capacity.
• Locate the dehumidier in an area where eld wiring
the control (low voltage) to the unit will be possible.
• It is recommended that a backdraft damper be
used in the discharge duct of the
Dehumidier, especially when connecting to the supply ducting system. The backdraft damper prevents supply
air from counter owing through the Dehumidier when it is not operating. The dehumidier’s
location should be chosen to allow installation of this accessory if necessary.
• The Dehumidier may be suspended from structural members with steel hanger straps or a suitable
alternative, ensuring the assembly supports the dehumidier’s base in its entirety. DO NOT hang the
Dehumidier from its cabinet.
• Allow for proper routing and drainage of needed drain pipes.
Electrical Service Access
(Either Side)
Filter
9' Power Cord
Top View
Minimum
Clearance
For Filter
(Either Side)
15"
6" Fresh Air Intake (Optional)
10" Return Air Duct
10" Supply Air Duct
A
B
C
B
C
Drain Port
A
6" Minimum Clearance
For Proper Airflow
DEHUMIDIFIER SET UP
Removal of Compressor Shipping Support
The Dehumidier uses a compressor to power the refrigeration
system. To protect the compressor and refrigeration system during
shipping, a plastic tie wrap secures it to the unit’s frame. Remove the
tie wrap by cutting the tie wrap and pulling from the unit as shown.
After removing tie wrap, insert plastic plugs provided into the holes.
CAUTION!CAUTION!
REMOVE COMPRESSOR SHIPPING TIE FROM THE UNIT. FAILURE TO REMOVE SHIPPING TIE
WILL CAUSE EXCESS VIBRATION TO BE TRANSMITTED TO THE FRAME.