Broan B98DHV 98 Pint Dehumidifier

Installation & Operation Instructions - Page 13

For B98DHV. Series: WHOLE-HOME SERIES
Also, The document are for others Broan models: B120DHV

PDF File Manual, 19 pages, Read Online | Download pdf file

B98DHV photo
Loading ...
Loading ...
Loading ...
13
800.558.1711 Installation & Operation Instructions
CONTROLS
Control Connections
The control and the Dehumidier are labeled to prevent confusion. Depending on the control, some of
the screw terminals on the Dehumidier may not be used. Be sure to consult the electrical schematic in
this manual or inside the access panel of the Dehumidier before
making control connections.
A low voltage control must be used with the Dehumidier.
NOTE: 18 gauge wire needed between the Dehumidier and the external control.
Compressor ON / Fan ON Make contact between 24V and DEHU terminals
Compressor OFF / Fan ON Make contact between 24V and FAN terminals
Power HVAC Accessory Connect the accessory to the DMPR (OR COM) and 24V terminals
Between the COM lead and the 24V TERMINAL is a 40VA transformer. This low voltage power source
powers the relay coils which control the fan and compressors. This 24VAC transformer can also be
used to power HVAC accessories external to the dehumidier.
COM 24VAC Power Transformer Neutral Side
FAN Fan Control
24V Transformer High Side
DEHU Dehumidication (Fan and Compressor) Control
DMPR 24VAC Power Transforme Neutral Side
* Spare Terminal (Open)
B98DHV Terminal Block Control Operation:
COM 24VAC Power Transformer Neutral Side
FAN Fan Control
24V Transformer High Side
DEHU Dehumidication (Fan and Compressor) Control
FLOAT External Low Voltage Float Switch or Water Sensor
(Use Normally Closed Switch)
FLOAT External Low Voltage Float Switch or Water Sensor
(Use Normally Closed Switch)
B120DHV Terminal Block Control Operation:
Loading ...
Loading ...
Loading ...