58
4. Operation
Chg. cur. limiting coef. (C): The charging current limit is a multiple of the battery capacity. The value range is 0.05 to
0.25. The default value is 0.15. Consult the specic battery cabinet owner’s manual for the recommended Coecient
(Coef.) based on the S3M UPS model and battery cabinet model.
Celloatvoltage(V/Cell): The oat voltage value range is 2.20 to 2.29 V/cell. The default value is 2.27 V/cell.
Cell boost voltage (V/Cell): The battery equalized voltage value range is 2.30 to 2.40 V/cell. The default value is 2.35 V/
cell.
Aver Charging Duration (min): Boost charge time limit. The value range is 1 to 999 minutes. The default value is 240.
Consult the specic battery cabinet owner’s manual for the recommended Aver Charging Duration (min) based on the
S3M UPS model and battery cabinet model.
Figure 4-31B: Battery Settings
EOD Battery Volt (V/Cell): End of discharge voltage. The value range is 1.60 to 1.90. The default value is 1.67.
FloatTempCompenCoef.(V/Cell/°C): Modify the voltage of compensation after enabling the switch. The value range
is 0.001 to 0.007/cell. The default value is 0.003.
Boost Charge Setting: Boost charge setting is disable or enable. The default is enable.
No Battery Warning: When set to Disable, the buzzer will not sound. Set to Enable for audible battery warnings. The
default is enable.