4. Operation
4.3.6.2.2 Parallel Setup
Parallel ID: The Parallel ID must be modied after setting the work mode to parallel mode. The value range is 1 to 6.
The default value is 1.
Parallel for Capacity Units: Parallel cabinet number must be modied for the total number of parallel cabinets after
setting the work mode to parallel mode. The value range is 2 to 6. The default value is 2.
Parallel Redundancy Units: Parallel redundancy cabinet number can be modied after setting the work mode to
parallel mode. The value range is 0 to 5. The default value is 0.
Figure 4-29: Parallel Settings
4.3.6.2.3 Output Setup
Output Freq (Hz): Output frequency. The value can be 50 Hz or 60 Hz. Default value is 60 Hz.
Output Volt Level (V): Output voltage level. The value can be 120 or 127. Default value is 120.
Inverter Volt Adjust (%): Inverter voltage regulated. The value can be -5% - 0 - +5%, in increments of 0.5%. The default
value is 0.
Figure 4-30: Output Settings