3. Installation and Wiring
Multiple Battery Pack Connections
CAUTION!
Ensurecorrectpolarityofthebatterystringseriesconnection.DONOTmixbatterieswithdierent
capacityordierentbrands,orneworoldbatteries.
WARNING!
Ensure correct polarity of string end connections to the battery circuit breaker, and from the
battery circuit breaker to the UPS terminals (i.e., (+) to (+) / (-) to (-) / (N) TO (N)). Disconnect one or
more battery cell links in each tier. do not reconnect these links and do not close the battery circuit
breaker unless all connections are properly checked and approved.
Note:Pleaserefertosection4.3.6.2.4forinformationonconguringthebatteryAhcapacity,thenumber
of batteries and the number of battery cabinets.