6
EN
www.napoleon.com
N415-0543 JUL 17.20
CYLINDER SIZE OPENING A AREA OPENING B
AREA
20 lb (9.1kg)
20in
2
(130cm
2
) 10in
2
(65cm
2
)
30 lb (13.6kg)
30in
2
(195cm
2
) 15in
2
(100cm
2
)
rigid pipe, copper tube or an approved exible metal connector which complies with Z21.24/ CSA 6.10 or
ANSI Z21.75/CSA 6.27.
The installaon must comply with CAN B149.1 Natural Gas and Propane installaon code in Canada, or
to the Naonal Fuel Gas code, ANSI Z223.1 in the United States. The gas supply pipe must be suciently
sized to supply the BTU/h specied on the rang plate, based on the length of the piping run. If installing
a side burner, a separate line must be branched o to the side burner unit and enter the side burner
opening at the specied locaon. If the enclosure is to house a propane cylinder, the tank poron of the
enclosure must be venlated according to local codes, and must not have communicaon with the cavity
used to enclose the gas grill. A propane cylinder can not be stored below the gas grill.
BUILT IN CYLINDER ENCLOSURES: Built in cylinder enclosures which completely enclose the cylinder must
have both of the following:
1. At least one unobstructed venlaon opening on the exposed exterior side of the enclosure located
within 5 in (127mm) of the top of the enclosure. The opening must have a total free area of more than 20
in
2
(130 cm
2
) for a 20 lb (9.1 kg) cylinder and 30 in
2
(195 cm
2
) for a 30 lb (13.6 kg) cylinder.
2. At least one venlaon opening on the exposed, exterior side of the enclosure located 1 in (25.4 mm) or
less from the oor level. The opening must have a total free area of more than 10 in
2
(65 cm
2
) for a 20 lb
(9.1 kg) cylinder and 15 in
2
(100 cm
2
) for a 30 lb (13.6 kg) cylinder. The upper edge must be no more than
5 in (127 mm) above the oor level.
Every opening must be large enough to permit the entrance of a 1/8 in (3.2 mm) rod.
WARNING!
• The cylinder valve(s) must be readily accessible for hand operaon. A door on the enclosure to
gain access to the cylinder valves is acceptable, provided it is non-locking and can be opened
without the use of tools.
• The enclosure for the LP-gas cylinder must isolate the cylinder from the burner compartment to
provide shielding from radiaon, a ame barrier, and protecon from foreign material,
such as hot
drippings. The
enclosure cannot be located directly below the grill.
• There must be a minimum clearance of 2 in (51 mm) between the oor of the LP-gas cylinder
enclosure and the ground.
• The enclosure must be designed so that the LP-gas cylinder can be connected, disconnected and
the connecons inspected and tested outside the cylinder enclosure. Any connecons that can
be disturbed when installing the cylinder in the enclosure must be accessible for tesng inside the
enclosure.
5” (127mm)
MAXIMUM
1” (25.4mm)
MAXIMUM
OPENING
A
OPENING
B
2” (51mm)
MINIMUM
PARTITION TO ISOLATE
CYLINDER FROM GRILL
NON LOCKING DOOR
34” (864mm)
RECOMMENDED
5” (127mm)
MAXIMUM
!