SEQUENCE OF OPERATION
PAGE 27
ENGLISH
procedure and the user can use it normally.
2. If you have entered the self-check program, you need to
power o the machine, power on again, wait for the internal
machine CC display, then skip the self-check program
operation.
Part 4:
Test mode for manual measurements
1. Run refrigeration through NewFI according to the
following table parameters.
Full Parameters
Compressor
Setting (Hz)
Fan Speed Set-
ting (RPM)
Exhaust Temp
Setting (°C)
AW24TL2HFA* 40 900 62
AW30TL2HFA* 59 900 70
AW36TL2HFA* 72 900 73
2. After the machine runs for 20 minutes, judge whether
the operating parameters of the machine are in the normal
range according to the parameters in the following table.
A. The outer ring temperature is less than 10 degrees.
Check
Parameters
Suction
Temp.
Exhaust
Temp.
IDU Coil
Temp.
IDU Outlet
Temp.
AW24TL2HFA* <10°C 55°C~70°C 4°C~10°C 6°C~14°C
AW30TL2HFA* <10°C 65°C~75°C 4°C~10°C 6°C~14°C
AW36TL2HFA* <10°C 68°C~78°C 4°C~10°C 6°C~14°C
B. The outer ring temperature is greater than 10 degrees
and less than 30 degrees.
Check
Parameters
Suction
Temp.
Exhaust
Temp.
IDU Coil
Temp.
IDU Outlet
Temp.
AW24TL2HFA* 2°C~10°C 55°C~70°C 8°C~14°C 10°C~15°C
AW30TL2HFA* 2°C~10°C 65°C~75°C 8°C~14°C 10°C~15°C
AW36TL2HFA* 2°C~10°C 68°C~78°C 8°C~14°C 10°C~15°C
C. The outer ring temperature is greater than 30 degrees
Check
Parameters
Suction
Temp.
Exhaust
Temp.
IDU Coil
Temp.
IDU Outlet
Temp.
AW24TL2HFA* 4°C~15°C 55°C~70°C 8°C~18°C 10°C~20°C
AW30TL2HFA* 4°C~15°C 65°C~75°C 8°C~18°C 10°C~20°C
AW36TL2HFA* 4°C~15°C 68°C~78°C 8°C~18°C 10°C~20°C
NOTE: The actual temperature parameters in the United
States are for reference only.