SEQUENCE OF OPERATION
PAGE 26
ENGLISH
Guide:
1. Apply power to the unit.
2. Set to Cooling Mode or Heating Mode.
3. Set the temperature to 75°F.
4. Press the SLEEP button 7 times within 5 seconds. Indoor
PCB will Beep 2 times to conrm.
5. 75°F will be the starting/reference point for the Tempera-
ture Compensation. Temperature Compensation can be
adjusted from -8° to +6° . Example: if you want to set the Tem-
perature Compensation value by 4°, then set the temperature
to 79°F.
6. Once the desired value has been selected, turn OFF the unit
via the YR-HG controller to save the compensation settings.
SmartHQ
The Bluetooth module will connect to the unit physically via
RJ45 (Service Port), and connect to the laptop via USB.
We can use it to achieve the following SmartHQ functions:
1. Software Updates
2. Real Time Sensor Readings / Load Control
3. View Alerts, Fault Data, Cycle History, Graphs
4. Automated Diagnostic Tests
5. Data Collection
Estar6.1
1. Energy Star self-inspection mode entry mode Use remote
control is to use remote control to enter arbitrary xed
frequency mode.
Fixed frequency mode:
1) Remote control refrigeration high wind, set to 60°F, press
the sleep button 4 times continuously within 7 seconds, the
inner machine will echo 5 times.
2) Remote control heating high wind, set to 86°F, press the
sleep button 4 times continuously within 7 seconds, the
inner machine echoes 5 times
2. Skip once Indoor unit (trigger controller includes remote
controller and wire controller):
The internal machine receives any Skip trigger signal:
1) Set the air supply mode and then change the current
wind speed;
2) If no trigger signal is received within 10 minutes after the
power-on enters the self-test mode, it will automatically
trigger and skip once; Symptom: The internal machine
displays JP and enters standby mode after 5S.
3. Permanently skip the Bypass function Indoor unit (trigger
controller includes remote controller and wire controller):
Internal machine receives Bypass signal:
1) Set dehumidication to 20 ° C (68 ° F) Symptom: The
internal machine displays BP and enters standby mode
after 5S.
After the product is installed and powered on for the rst
time, conrm e-star by following instructions.
Part 1:
Determine whether the e-star installation program is
required:
1. If CC is displayed alternately on the dual-8 display
boards of the indoor unit during the initial power-on, it
indicates that the machine can be used normally only after
conrmation of the e-STAR installation program.
2. If CC is not displayed alternately on the dual-8 display
boards of the indoor unit during the initial power-on,
the e-STAR installation program does not need to be
conrmed.
Part 2:
How to enter the self-test procedure:
When the indoor unit double 8 display board alternately
displays CC. Perform the following steps to enter the self-test
procedure.
Remote control Settings: In cooling or heating mode, set the
temperature to 25 degrees Celsius or 77 degrees Fahrenheit.
The machine will enter the following operation mode:
A. When outdoor ambient temperature Tao > 75F, the air
supply mode of indoor unit at n1 stage (running “Start,
air supply, high wind”) runs for 3min; N2 stage; N3 stage
cooling mode (run “start up, cool, high wind, 16 degrees”)
Run for 15min N3 (blink once every 1 second).
B. When the outdoor ring temperature is 14F≤Tao≤75F,
the air supply mode of the indoor unit at n1 stage (running
“Start, air supply, high air”) runs for 3min; N2 heating
mode (heating, high wind, 30 degrees) runs for 10min,
N2 (ashing once every 1 second), indoor to outdoor
send “start, heating, high wind, 30 degrees”; N3 stage
refrigeration mode (running “refrigeration, high wind, 16
degrees”) for 10min, N3 (ashing once every 1 second),
indoor to outdoor send “startup, refrigeration, high wind,
16 degrees”.
C. When outdoor ambient temperature Tao < 14F, the
indoor unit air supply mode (running “start, air supply, high
wind”) at n1 stage runs for 3min; N2 stage heating mode
operation (running “heating, high wind, 30 degrees”) 15min
N2 (ashing once every second), no in N3 stage.
Note: Air supply mode, run for 3 minutes, display FN-N1
alternately on hanging panel; After the test is completed, the
internal machine panel shows PS, proving that the machine
has passed the self-test operation. The user can press any
button to exit the selftest and use the function normally.
Part 3:
How to skip the self-test procedure:
1. When CC is displayed on the internal machine, set by
remote control: press dehumidication mode when the
temperature is set to 20 degrees Celsius or 68 degrees
Fahrenheit. After setting, the hanging panel will display
bP, indicating that the machine has skipped the self-check