Side Mount Models Installation
SIDE MOUNT WIRING AND ELECTRICAL CONNECTIONS
INSTALLING UNIT TO WALL PANEL
Position the unit as close as possible to the walk-in before removing from the shipping skid.
Remove the system from the shipping skid and carefully slide the unit into the wall panel opening.
Level the unit by adjusting the leveling legs.
There are rivnuts around the perimeter of the opening. Using the supplied bolts, attach the unit to the walk-in by
the flange around the evaporator compartment.
Tighten the bolts until the gasket material is compressed to a thickness of approximately 1/8”/3mm.
Apply a 3/8”/10mm bead of silicone around the perimeter of the evaporator compartment to ensure an air tight
seal.
All electrical connections and routing must comply with local and national codes.
Do not modify the factory installed wiring without written factory approval.
Refer to the serial plate on the unit to determine the proper electrical power supply.
Wire type should be of copper conductor only and properly sized to handle the electrical load.
Unit wiring diagrams are attached inside the electrical box cover.
The electrical box is located behind the condensing unit housing side panel.
The Side Mount Unit is top heavy and can easily tip over causing injury and unit damage!
All wiring must comply with local and national codes. Wiring must be performed only by a refrigeration technician or
certified electrician. Failure to follow these guidelines may result in injury!
Check all wiring connections, including factory terminals, before operation. Connections can become loose
during shipment and installation.