Kolpak P8-1208-CT Walk-In Cooler & Top Mounted Compressor

Polar pak installation - Page 8

For P8-1208-CT.

PDF File Manual, 33 pages, Read Online | Download pdf file

P8-1208-CT photo
Loading ...
Loading ...
Loading ...
8
Remove the diagonal shipping braces from the condensing and louvered ends of the unit.
All electrical connections and routing must comply with local and national codes.
Do not modify the factory installed wiring without written factory approval.
Refer to the serial plate on the unit to determine the proper electrical power supply.
Wire type should be of copper conductor only and properly sized to handle the electrical load.
Unit wiring diagrams are attached inside the electrical box cover.
The electrical box is located behind the condensing unit housing louver.
TOP MOUNT DRAIN LINE OUTDOOR MODELS ONLY
Connect a copper drain line to the evaporator drain using a compression fitting. Do not reduce the drain line size.
Slope the drain line a minimum of ½”/13mm per foot to allow proper drainage.
The drain line must be wrapped with heat tape and insulated with a minimum ½”/13mm thick Armaflex.
Install a P-trap in the drain line to prevent the suction of ambient temperatures into the evaporator compartment
which can lead to excessive humidity and icing issues.
Check all wiring connections, including factory terminals, before operation. Connections can become loose during shipment
and installation.