Kolpak P8-1208-CT Walk-In Cooler & Top Mounted Compressor

Polar pak installation - Page 5

For P8-1208-CT.

PDF File Manual, 33 pages, Read Online | Download pdf file

P8-1208-CT photo
Loading ...
Loading ...
Loading ...
5
Section 2
Installation
Walk-In Installation
Installation and operation instructions for the walk-in are provided separately. A copy of this manual can be obtained
from the website at www.kolpak.com or by calling technical service at 800-225-9916.
Clearance Requirements
A minimum of 18”/46cm clearance is required on all sides of the unit to allow proper air flow and serviceability of
the system.
A supply of clean ambient air or ventilated air is required to maintain acceptable condensing temperatures (less
than 110°F/43°C ambient) and allow removal of heated discharge air from the condensing unit area.
Building Wall
18”/46cm Minimum Drop-In Refrigeration Unit
18”/46cm Minimum
Building Wall
Example of Minimum Clearance Requirements
Failure to observe clearance and air flow requirements will result in poor system performance, premature equipment
failure, and inability to service the system!