1. Before starting, the licensed electrician should consult all applicable
codes for breaker and wire sizing requirements. Set the amperage of
the unit according to the connected dedicated breaker associated
with the hardwired connection or NEMA outlet. Using the table above,
determine the voltage and amperage of the installation. Then, set
the unit’s DIP switch following the diagram below that corresponds
with the dedicated breakers voltage and amperage and the model’s
requirements.
20A 3.8kW 208V/240V 16A Y Y
30A 5.8kW 208V/240V 24A Y Y
40A 7.7kW 208V/240V 32A Y Y
50A 9.6kW 208V/240V 40A Y Y
60A 11.5kW 208V/240V 48A Y N
70A 12.0kW 208V/240V 50A Y N
80A 12.0kW 208V/240V 50A Y N
Dedicated
Breaker Kilowatts Voltage Amperage Hardwired Plug
30A BREAKER 240V 24A
50A BREAKER 240V 40A
70A BREAKER 240V 50A**
20A BREAKER 240V 16A 40A BREAKER 240V 32A*
Factory setting
60A BREAKER 240V 48A**
80A BREAKER 240V 50A**
FINAL STEPS
* All models’ default current settings are set to 32A.
**Models SEV1600P1450 and SEV1600P650 should
not use a current setting greater than 40A.
For models SEV1600HW, SEV1600P1450, and SEV1600P650, the
following steps must be completed by a licensed electrician.