gate or ball
valve on inlet
lter
1. Turn off the water inlet supply valve.
2. Open a hot water tap to release the line pressure.
3. Remove the lter by turning it counterclockwise. Clean
under running water with an old toothbrush then replace.
NOTE: This filter is designed to be cleaned as part of
regular maintenance.
Kelvinator Gas Continuous Flow hot water system water connection 11
Water connection
warning
Do not reverse the hot outlet and cold supply line
connections to the water heater as this will cause your
heater to operate improperly.
gate or ball
valve on inlet
drain plug
lter
All pipes, pipe ttings, valves and other components,
including soldering materials, must be suitable for
potable water systems.
A manual shut off valve must be installed on the cold
water inlet to the water heater between the main water
supply line and the water heater.
Only a gate valve or a ball valve is to be used on the cold
water supply.
Check that the cold water pressure is sufcient for the
water heater. If it is above 1000kPa an approved pressure
limiting valve must be tted to the installation.
Before installing the water heater, ush the water line
to remove all debris, and after installation is complete,
purge the air from the line. Failure to do so may cause
damage to the water heater.
There is a wire mesh lter on the water heater cold inlet
to prevent debris from entering the water heater. Clean
the lter after initial installation to ensure it has not
been blocked.
hot water
outlet
cold water
intlet
lter