While the liners must be continuous from the appliance to the chimney cap,
to achieve the needed length, they may be coupled, using an approved
coupler and sealant.
We recommend that exhaust vents that pass through unheated spaces,
such as tall exterior chimneys, be wrapped in a protective sleeve to minimize
condensation and reverse flow symptoms. See "TROUBLESHOOTING"
section for details.
This appliance is approved for use with a 3" (76mm) exhaust and air intake.
A. OUTSIDE: Slip the one end of a liner a minimum of 2" (51mm)
over the sleeve of the air terminal. Secure using 3 screws. Then
seal the joint and screw heads with high temperature sealant. Repeat with the other liner.
NOTE: We recommend that the other end of the exhaust liner be marked to eliminate the
exhaust liner being connected to the intake collar at the appliance.
B. Gently stretch the liners to the
required lengths and insert into
the chimney. Trim and fit the
flashing plate to suit the chimney
termination. Place the air terminal
onto the top of the chimney.
Make weather tight by sealing
with caulking (not supplied).
Fasten to the chimney with
screws and plugs (not supplied).
C. INSIDE: Remove the securing
screw from the front of the vent
mounting plate. Pull the vent
mounting plate only, back into
the track, to the front stop. Start
the slider back into position.
Re-secure the screw. The
appliance may now be pushed
into its final position inside the
wood burning appliance, and the
screw tightened until the slider
has been pulled tight to the front
stop.
D. Route the flex liners through the
slider. Attach and secure the liners to the vent mounting plate using the same procedure as before,
ensuring that the marked exhaust liner is attached to the exhaust collar.
FLASHING
PLATE
2” (50.8mm)
OVERLAP
MILL-PAC
INTAKE
EXHAUST
SECURING
SCREW
SLIDER
MOUNTING
PLATE
HIGH TEMP
SEALANT
2” (50.8mm)
OVERLAP
LINERS
EXHAUST
INTAKE
VENT MOUNT
ASSEMBLY
SAFETY BARRIER
3.2 CHIMNEY CONNECTION
Chimney installation must conform to both national and local code requirements. The chimney must be lined
with one 3" (76mm) diameter liner for intake and one 3" (76mm) diameter liner for exhaust. The minimum and
maximum vent lengths are 10 feet (3m) and 35 feet (11m) respectively.
Recommended kits come in 3 lengths:
2-3" DOUBLE PLY ALUMINUM LINER-INLET AND EXHAUST:
GDI-320KT VENT KIT 20FT (6m)
GDI-325KT VENT KIT 25 FT (7m)
GDI-335KT VENT KIT 35 FT (11m)