Fire Magic 3281L

User Manual - Page 9

For 3281L.

PDF File Manual, 28 pages, Read Online | Download pdf file

3281L photo
Loading ...
Loading ...
Loading ...
9
Installation must be performed by a qualifi ed professional
service technician.
This unit is designed for outdoor use only. DO NOT use this unit
inside a building, garage, enclosed area, or under overhead
combustible construction.
See below for details on installing under non-combustible
overhead construction.
DO NOT use this unit in or on a recreational vehicle or boat.
Important: If installing this unit in a combustible enclosure, the
correct air gap requirement must be met.
Important: Refer to the information below to ensure all
required clearances are met.
The unit must have a minimum clearance of 18" from
combustible materials/items AT ALL TIMES.
Overhead Construction Requirements (if applicable)
This outdoor cooking gas appliance shall not be used under
overhead combustible construction.
A minimum clearance of 5 feet is required between the countertop
and the non-combustible construction above (Fig. 9-1).
Side and Rear Wall Clearances
For the minimum clearances between the sideburner and any side or
rear walls, your setup must fall within one (or more) of the following:
A. Clearance between sideburner and strictly non-
combustible wall
(i.e. brick wall, see Fig. 9-2)
The unit must have a minimum of 4" right, left, and rear
clearance from any non-combustible wall.
(To allow for proper ventilation and prevent dangerous
overheating.)
B. Clearance between sideburner and a protected
combustible wall
(i.e. a non-combustible wall in front of a combustible wall to
serve as a barrier. This can be accomplished by brick, or a metal
stud fi nished with non-combustible substrate, see Fig. 9-3)
The unit must have a minimum of 14" right, left, and rear
clearance from the protected combustible wall.
(The 4" non-combustible material plus an additional 10"
clearance between the sideburner and protected wall.)
C. Clearance between sideburner and combustible wall
The unit must have a minimum of 18" right, left, and rear
clearance from any combustible wall (see Fig. 9-4).
Backsplash (if applicable)
If a non-combustible backsplash exists, it must have a minimum of a
4" clearance from the rear of the unit (to allow for proper ventilation
and prevent dangerous overheating). See Fig. 9-5.
Important: This 4" backsplash clearance must fi rst be met prior
to any non-combustible walls beginning behind it.
Min.
14"
Min.
18"
Min.
4"
Fig. 9-2 Clearance 'A' Diagram
Fig. 9-3 Clearance 'B' Diagram
Fig. 9-4 Clearance 'C' Diagram
Non-combustible
Non-combustible
substrate
Non-combustible 4"
Combustible
(Clearance required for
right, left, and rear)
Fig. 9-5 Backsplash clearance
Non-combustible
Backsplash
Com-
bustible
(Clearance required for
right, left, and rear)
(Clearance required for
right, left, and rear)
Fig. 9-1 Overhead requirements
Min.
5'
Min.
4"
INSTALLATION REQUIREMENTS
NON-COMBUSTIBLE
CONSTRUCTION ONLY
REV 0 - 1601191055
L-C2-448
Loading ...
Loading ...
Loading ...