Napoleon B36NTR Ascent Series Direct Vent Natural Gas Fireplace

User Manual - Page 36

For B36NTR.

PDF File Manual, 160 pages, Read Online | Download pdf file

B36NTR photo
Loading ...
Loading ...
Loading ...
36
W415-1401 / C / 03.18.15
EN
35 1/2"
902mm
49 1/8"
1248mm
31 7/8"
810mm
It is best to frame your appliance after it is positioned and the vent system is installed. Frame to local building
codes.
It is not necessary to install a hearth extension with this appliance.
When roughing in the appliance, raise the appliance to accommodate for the thickness of the nished oor
materials, i.e. tile, carpeting, hard wood, which if not planned for will interfere with the opening of the lower
access door and the installation of many decorative ashing accessories.
Combustible materials may be installed ush with the front of the appliance but must not cover any of the black
face-areas of the appliance. Non-combustible material (brick, stone or ceramic tile) may protrude in these areas.
Minimum clearance to combustible construction from appliance and vent surfaces:
Combustible Framing:
- 0" to stand-offs
- 1" (25mm) to bottom and sides of the vent pipe*
- 3" (76mm) to top of the vent pipe*
Combustible Finishing:
- 0" to rear stand offs
- 0" to front face top and sides
Top Exit
- 50 1/2" (1283mm) to combustible enclosure top from base of the appliance
- 54" (1372mm) to ceiling from base of the appliance
Rear Exit
- 41" (1041mm) to combustile enclosure top from base of the appliance
- 54" (1372mm) to ceiling from base of the appliance
*B36 HORIZONTAL VENT SECTIONS: A minimum of 1" (25mm) at the bottom and sides and 3" (76mm) at
the top of the vent pipe on all horizontal runs to combustibles is required. Use restop spacer W010-3440
(supplied).
NOTE: The minimum clearances from the top of the horizontal vent pipe to combustible materials may
be reduced from 3" (76mm) to 1" (25mm) in those installations with a minimum 38" (965mm) vertical
vent rise made immediately off the replace collar.
*B36 VERTICAL VENT SECTIONS: A minimum of 1" (25mm) all around the vent pipe on all vertical runs
to combustibles is required except for clearances in appliance enclosures. See "MINIMUM ENCLOSURE
CLEARANCES" section. Use restop spacer W500-0096 (not supplied).
INSIDE
CHASE
OUTSIDE
CHASE
SIDE
WALL
16”
406mm
16"
406mm
2"
51mm
35 1/2"
902mm
35 1/2"
902mm