Napoleon B36NTR Ascent Series Direct Vent Natural Gas Fireplace

User Manual - Page 23

For B36NTR.

PDF File Manual, 160 pages, Read Online | Download pdf file

B36NTR photo
Loading ...
Loading ...
Loading ...
23
W415-1401 / C / 03.18.15
EN
3.11 REAR EXIT
!
WARNING
FAILURE TO INSTALL THE CAP WILL CAUSE THE APPLIANCE TO FUNCTION IMPROPERLY AND
CAN CAUSE INJURY OR PROPERTY DAMAGE.
A. Remove the safety screen and glass front, refer to "
SAFETY SCREEN & DOOR REMOVAL / INSTALLATION"
section.
B. Remove the contents from the rebox and set aside, you
will need the exhaust ue collar from the top of the log
carton.
C. To ease assembly, remove the four hex head screws
securing the de ector from inside the top front of the rebox, refer to Figure 1.
D. Place the gasket (provided) over the 4" (102mm) ue collar assembly and
bend along perforation.
E. From inside the rebox, insert the 4" (102mm) ue collar through the back
of the rebox. Secure the ue collar assembly and gasket using the four
hex head 3/8" thread cutting screws, refer to Figure 2. NOTE: Do not
overtighten. The gasket needs only to be snug against the rebox.
F. Re-attach the de ector using the four screws and install the log set, glass
door and safety screen.
Fig. 2
DEFLECTOR
90°
V
1
V
2
H
1
H
2
90°
90°
H
3
45°
18.2_3A
Example:
V
1
= 1.5 FT (0.5m)
V
2
= 5 FT (1.5m)
V
T
= V
1
+ V
2
= 1.5FT (0.5m)+ 5FT (1.5m) = 6.5 FT (2m)
H
1
= 1 FT (0.3m)
H
2
= 1 FT (0.3m)
H
3
= 10.75 FT (3.3m)
H
R
= H
1
+ H
2
+ H
3
= 1FT (0.3m) + 1FT (0.3m) + 10.75FT (3.3m) = 12.75FT (3.9m)
H
O
= .03 (four 90° elbows + one 45° elbow - 90°)
= .03 (360° + 45° - 90°) = 6.75 FT (2.1m)
H
T
= H
R
+ H
O
= 12.75FT (3.9m) + 6.75FT (2.1m) = 19.5 FT (5.9m)
H
T
+ V
T
= 19.5FT (5.9m) + 6.5FT (2m) = 26 FT (7.9m)
Formula 1:
H
T
< 3 V
T
3 V
T
= 3FT (0.9m) x 6.5FT (2m) = 19.5FT (5.9m)
19.5FT (5.9m) = 19.5FT (5.9m)
Formula 2:
H
T
+ V
T
< 40 FT (12.2m)
26 FT (7.9m) < 40 FT (12.2m)
Since both formulas are met, this vent configuration is acceptable.
Fig. 1
NOTE: A #42 ori ce was supplied with your appliance. In installations with a vertical rise greater than
8" (203mm) in the vent con guration, the #42 ori ce must be used to increase the ame size.