D. MAKE FOUR-WIRE
ELECTRICAL CONNECTION
TO DIRECT WIRE
If making a direct wire connection:
Electrical Shock Hazard
Turn power supply off before
connecting wires.
Use 10 gauge solid copper wire.
Electrically ground dryer.
Failure to follow these instructions
can result in death, fire, or electrical
shock.
The dryer can be connected directly
to fused disconnect or circuit breaker
box with four-wire flexible armored or
non-metallic sheathed copper cable
(with grounding wire). All current-carrying
wires must be insulated.
A conduit connector must be installed
at junction box. Allow four feet of slack
in the line so dryer can be moved if
servicing is ever necessary.
STEP 1. Turn power supply off.
STEP la. Strip 5 inches of outer covering
from end of cable. Leave bare grounding
wire at 5 inches.
i_ 5" _-_
I--
STEP lb. Strip 11/2inches from
3 remaining insulated wires. Strip
insulation back 1 inch. Shape the end
of each wire into a "U" shaped hook.
?
STEP 2. Remove hold-down screw
and terrninal block cover.
Hold-down
screw
Terminalblockcover
STEP 3. Attach 3/4"U.L.-listed strain
relief (U.L. marking on strain relief) to
the hole below terminal block opening.
Put the direct wire cable through the
strain relief.
STEP 4. Remove the center terminal
block ,,screw.Remove the neutral grounding
wire (!green/yellow wire) from external
grounding screw.
External !lr0und
connectol
Centersilver-colored
terminalblockscrew
r
6reen/yellow wire
cf harness
14