Ashley AGVF340N 1,200 Sq. Ft. Single-Burner Vent Free Natural Gas Stove

User Manual - Page 15

For AGVF340N.

PDF File Manual, 28 pages, Download pdf file

Loading ...
Loading ...
Loading ...
© 2020 United States Stove Company
15
INSTALLATION
SOLID FUEL BURNING FIREPLACES
INSTALLATION
This model may be installed in a masonry replace.
The gure below demonstrates the required
dimensions.
NOTE: See “Producing Adequate Air for Combustion
And Ventilation” section of this manual.
NOTE: Installer of this appliance must mechanically
(peel and stick) attach marking supplied with this
unvented appliance before installing to inside
of rebox of solid-fuel burning replace or listed
ventless rebox enclosure into which unvented
replace insert is installed (see the “Gas Pressure
Check” section of this manual).
CAUTION:
CUTTING ANY SHEET-METAL PARTS OF
A SOLID-FUEL BURNING FIREPLACE OR
LISTED VENTLESS ENCLOSURE IN WHICH AN
UNVENTED FIREPLACE IS TO BE INSTALLED IS
PROHIBITED.
NOTE: If the factory-built replace has no gas
access hole(s) provided, an access hole of 1.5” (37.5)
diameter or less may be drilled through lower
sides or bottom of rebox in a proper workmanlike
manner. This access hole must be plugged with
non-combustible insulation after the gas supply
line has been installed.
Refractory, glass doors, screen rails, screen mesh,
and solid-fuel log grates (if applicable) can be
removed from the replace before installing an
unvented replace insert.
NOTE: After the unit is positioned in the replace,
mark the trim panels as follows:
A. Set the side panels in place, at against the
replace. Mark a line down the inside edge of
the trim panel to make a vertical reference line.
24"
7"
25 - 1/8
35 - 9/16
13 - 3/4
7"
20"
CAUTION:
TRIM PANELS OR SURROUNDS SHALL NOT
SEAL VENTILATION OPENINGS IN THE
FIREPLACE.
ATTENTION:
SMOKE SHELVES, SHIELDS, AND BAFFLES MAY
BE REMOVED IF ATTACHED BY MECHANICAL
FASTENERS.
ZERO CLEARANCE INSTALLATION
The installation must conform with local codes or in
the absence of local codes, with National Fuel Gas
Code, ANSI Z223.1/NFPA54.
This appliance may be installed in an After-Market*
Manufactured (Mobile) Home, where not prohibited
by state or local codes.
* (After Market: Completion of sale, not for
purpose of resale from manufacturer).
This appliance is only for use with the type of gas
indicated on the certication plate. This appliance
is not convertible for use with other gases.
NOTE: See “Producing Adequate Air For Combustion
And Ventilation”
CHOOSING THE LOCATION FOR YOUR
FIREPLACE
The provided gures show some of the many ways
your replace may be installed. Consider trafc
patterns in your room and location of doors and
windows. Moving air from ceiling fans, open doors,
and hot air grills may cause ames to soot. If a
disturbance is found that affects ames, it must be
eliminated by turning off the ceiling fan, closing
door or closing or moving hot air register. A corner
location may be best where space is limited.
Your replace weighs no more than some of your
ne furniture. If the replace is located near a load-
bearing wall, additional supports to the foundation
will not be necessary. HEAVY FACINGS, SUCH AS
BRICK, STONE, ETC., MAY REQUIRE ADDITIONAL
FOUNDATION SUPPORT.
NOTE: If this appliance is installed directly on
carpeting, tile or other combustible material, other
than wood ooring, the appliance shall be installed
on a metal or wood panel extending full width and
depth of the appliance.