Repair Section
49
8.5 Inspection of Capacitor (for Fan Motor and Compressor)
(1) Ohmmeter method
Set the ohm-meter to the 10M range. Place the
two probes against the two terminals of the
capacitor. At first, the ohm-meter should
indicate small value, then the reading should
gradually increase towards infinity. This
indicates that the capacitor is charging. If the
reading indicates infinity right away (open) or
the ohm-meter fails to move from 0. (shorted),
replace the capacitor.
(2) Capacitance tester method
Using a capacitance tester and the chart on page 21, test the capacitor for the value indicated.
If the value tested is not within 10 % of indicated capacitance, replace the capacitor.
WARNING
Properly discharge the capacitor(s) before testing and after testing has been completed.
Failure to do so could cause damage to test equipment or the unit and/or result in
personal injury (electrical shock) or death.
8.6 Inspection of Drain Switch
Check for continuity between terminals 1 and 2
when drain switch is pressed. With drain switch
depressed, there is no continuity between
terminals 1 and 2. Replace drain switch if
continuity does not satisfy the above condition.
I001808
I001809
2
NC
C
1
DS2
DS1
To J103
Drain Switch
Top of Base Plate