Operation Section
22
(2) Relay board
The relay board receives signals and outputs
from the control board that contains a
microprocessor. The relay board contains the
compressor, fan on and fan mode (speed)
relays.
It also contains a step-down transformer that
converts the line voltage (208/230 VAC) to
12 V.
This 12 V is then converted from AC to DC and
used for relay coil activation. The 12 V (DC) power is sent to the control panel assembly where
it is further reduced to 5 V for the system logic.
The relay board also contains the DIP switch.
The DIP switch is used to change the fan mode operation from stop to operate and change both
the set point and room temperature display from Fahrenheit to Celsius.
< NOTE >
The relay board must be serviced as a complete assembly. It has only one serviceable
component, the fuse. (see below)
(3) Relay board fuse
This fuse provides protection against damage
to the step-down transformer. It must be
replaced with the exact type of fuse or an
equivalent.
Specifications:
- 2/10 A, 250 V
CAUTION
Failure to use the exact type of fuse could result in damage to the unit and/or to components. It
could also void the warranty of the unit.
I001772
Dip Switch
<Dip Switch>
Fan Mode Control
Switch
(STOP
OPERATE)
Temperature Scale
Display Switch
(°C
°F)
I001773
Fuse
<Relay Board>