Weil-McLain ECO TEC 199-C Residential Boilers

Manual - Page 94

For ECO TEC 199-C.

PDF File Manual, 156 pages, Read Online | Download pdf file

ECO TEC 199-C photo
Loading ...
Loading ...
Loading ...
Part number 550-100-260/0520
94
ECO
®
Tec
GAS-FIRED WATER BOILER80/110/150/199 BOILER MANUAL
DIAGNOSTIC menu
฀ DIAGNOSTICS menu



Current operating status of the boiler. Prepurge, Ignition, Name of the system Type being satisfied, post purge, Warm Weather
Shut down, Trouble
฀Out1
Temperature of the first sensing element of the boiler’s heat exchanger outlet sensor
฀
Temperature of the second sensing element of the boiler’s heat exchanger outlet sensor
฀
Temperature of the first sensing element of the boiler’s Combi DHW outlet sensor
฀
Temperature of the second sensing element of the boiler’s Combi DHW outlet sensor
Boiler฀In
Temperature of the boiler’s heat exchanger inlet sensor
฀
Temperature of the system water after the boiler loop
฀
Temperature of the system water returning to the boiler loop

Temperature of the first sensing element of the boiler’s flue gas sensor

Temperature of the second sensing element of the boiler’s flue gas sensor

Temperature of the remote outdoor air temperature sensor
฀
Current target temperature of the active priority.


Current operating status of the boiler. Prepurge, Ignition, Name of the system Type being satisfied, post purge, Warm Weather
Shut down, Trouble
฀
Call for heat status on Input 1
฀
Call for heat status on Input 2 (Input 2 can be TT1 or 0-10VDC input)
฀
Call for heat status on Input 3
฀
Call for heat status on Input 4

Voltage input for target adjust or modulation
฀
External manual limit on low voltage terminal strip
฀
External auto limit on low voltage terminal strip
฀฀
Low water cutoff device (inside boiler jacket)
฀
Limit device (inside boiler jacket) that will shut off the boiler if flue pressure becomes too high
฀
J18 jumper circuit closed or open (flow switch, CAD, etc.)
฀
Feedback from blower
฀
Number indicating the presence and quality of the flame used to shut down or boost the boiler
฀
Approximate gallons per minute water flow passing through the Combi brazed plate.


Current operating status of the boiler. Prepurge, Ignition, Name of the system Type being satisfied, post purge, Warm Weather
Shut down, Trouble
฀
Control’s gas valve circuit status
฀
Control’s circulator 1 relay status
฀
Control’s circulator 2 relay status
฀
Control’s circulator 3 relay status
฀
Control’s circulator 4 relay status
฀
Boiler’s circulator
฀
Control’s signal controlling the blower speed
฀฀
Additional heat demand contact status

Alarm contact status
Loading ...
Loading ...
Loading ...