STANDARD FEATURES
CABINET
The AirBoss Series cabinet is constructed of 18 gauge steel with a gray polyester powder
coated finish that will compliment any decor. The entire cabinet is insulated with a sound-
absorbing insulation for cool, quiet comfort. All units come equipped with handles and
swivel casters for portability and convenient set-up.
ELECTRONIC THERMOSTAT
All Air Boss unit are equipped with a non-programmable electronic thermostat. When
power is connected to the unit, the thermostat will control the Air Boss to cool a space to
the desired temperature. The thermostat is also capable of controlling the fan to operate
automatically (when needed) or continuously. To protect the compressor from short-
cycling, there is a built-in, 4-minute time delay in the thermostat.
FAN SPEED CONTROL
A two position rocker switch, located next to the thermostat, provides the user with the
option of running the evaporator fan in high-speed or low-speed.
CONDENSATE RESERVOIR/PUMP
Air Boss units come equipped with a means for handling the condensate generated dur-
ing the cooling process. All models except the 5-ton models come equipped with a
Condensate Reservoir Tank, that captures the condensate from cooling. The tank can
then be easily removed from the unit and emptied as required.
The 5-ton Air Boss models come equipped with an Automatic Condensate Pump that
disposes of the condensate. The pump comes with a 25 foot long vinyl hose that allows
for the disposal of the condensate water to a drain. The automatic pump is capable of a
20ft lift, to handle just about any installation requirement.
CONDENSATE ALARM LIGHT
On the front of all Air Boss models, there is a Condensate Alarm Light (RED) located near
the thermostat. For models less than 5-tons, the light indicates that the condensate tank
is full and needs to be emptied. In the 5-ton Air Boss units (model PAC60) the light indi-
cates a condensate pump over-flow condition where the pump is either disabled, or inca-
pable of rejecting the condensate water, and must be serviced.
FILTERS
All Air Boss units are equipped with washable filters at the air intakes. 1/8” mesh air filters
located behind the evaporator return air grill serve to filter the air before it is cooled. A
1/2” aluminum mesh filter serves to protect the condenser coil from dust build-up. Both
filters can be easily removed and cleaned.
HIGH PRESSURE SAFETY SWITCH
Located on the back of the Air Boss unit is a manual re-set high pressure switch, used for
the protection of the compressor. If the condensing pressure exceeds the limit setting, the
cut-out shuts down the compressor, while the evaporator fan remains running. The com-
pressor can be re-started, once the condensing pressure has lowered, by depressing the
“RESET” button.
POWER CORDS
All Air boss units come with power cords, convenient connection and portability. All units
except the 5-ton models, and 3-phase models are equipped with LCDI for added safety
devices.