OceanAire PAC6012 60,050 BTU Portable Commercial Air Conditi

User Manual - Page 4

For PAC6012.

PDF File Manual, 32 pages, Read Online | Download pdf file

PAC6012 photo
Loading ...
Loading ...
Loading ...
2
AirBos
s
Deluxe Air-Cooled Portable Air Conditioners
Specifications subject to change without notice
MODEL: PAC
1211
1811
2412 3612 3632 3634 6012 6032 6034
Cooling Capacity
1
11,800
16,800
24,020 36,050 36,050 36,050 60,050 60,050 60,050
Voltage (V/Phase) at 60Hz 115/1
208-230/1 208-230/1 208-230/3 460/3 208-230/1 208-230/3 460/3
Cooling Amps
6
10.4
14.1
14.9 18.1 17.2 8.7 32.0 20.4 14.8
Cooling Watts
6
1180
1670
2700 3620 3620 3620 6000 6000 6000
In Rush Current (Amps)
77.5
100.5
90 140 122 122 169 140 140
Plug Type
5-15P
5-20P
6-20P 6-30P L15-30P L16-20P 6-50P L15-30P L16-20P
EER
3
10.0
10.0
8.9 10.0 10.0 10.0 10.0 10.0 10.0
Compressor HP
1
1 1/2
2333555
Compressor RLA
9.5
12.3
10.5 13.6 8.8 5.0 27.6 18.1 9.0
Compressor LRA
50
63
48 83 77 35 158 137 62
Evap CFM
4
400
600
810 1310 1310 1310 1950 1950 1950
Evap Motor HP
1/8
1/8
1/3 1/3 1/3
1/3
111
Evap Motor Watts
200
210
350 375 375 375 550 550 550
Condenser CFM
580
930
1010 1390 1390 1390 2200 2200 2200
Condenser Motor HP
1/8
1/8
1/3 1 1 1 1 1 1
Condenser Motor Watts
280
450
330 460 460 460 750 750 750
Condensate 5 Gallon Condensate Tank - STANDARD (Pump Optional) Pump -STANDARD (20 ft. Lift)
Sound Level
5
54 60
65 69 78
R-410A Charge Oz.
18 40
37 66 80
(A) Height with Casters (in.)
37
44 1/2
51
52
(B) Width (in.)
20 24
27
(C) Depth (in.) 25 30
35 39
(D) Height w/o Casters (in.) 32 1/2
39 1/2 45
46
Net Weight (lb.)
180
260
260
365
485 485 515
Shipping Weight (lb.)
200
285
285
405
525 525 555
Shipping Volume (cu. ft.)
19
28 40 48
380
420
SPECIFICATIONS
1. Cooling Capacity is total BTUH at 80ºDB/67ºWB return air,
95ºF Outdoor at high fan speed
2. Time Delay fuses/circuit breakers are recommended
3. EER is determined at high fan speed, with condenser
discharge air ducted into another area
4. CFM with free discharge
5. Sound Pressure, dB at 5 feet, commercial operation
6. Amps & Watts at 208 Volts
May operate down to 55º if equipped with hot gas bypass
(Factory installed)
Ambient operating range 65º to 105º
50 Hz MODELS AVAILABLE - CONSULT FACTORY
Note: Condenser inlet air plenum adds
13 inches to dimension “C”