52
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
ENGLISH
WARNING
• Regulation for refrigerant leakage
: the amount of refrigerant leakage should satisfy the following equation for human safety.
If the above equation can not be satisfied, then follow the following steps.
• Selection of air conditioning system: select one of the next
- Installation of effective opening part
- Reconfirmation of Outdoor Unit capacity and piping length
- Reduction of the amount of refrigerant
- Installation of 2 or more security device (alarm for gas leakage)
• Change Indoor Unit type
:
installation position should be over 2m(6.56ft) from the floor (Wall mounted type Cassette type)
• Adoption of ventilation system
: choose ordinary ventilation system or building ventilation system
• Limitation in piping work
: Prepare for earthquake and thermal stress
Liquid pipe
Low Pressure
Gas pipe
High Pressure
Gas pipe
Manifold Gauge
Low pressure side Handle
High pressure side Handle
Total amount of refrigerant in the system
0.44(kg/m
3
(0.028(lbs/ft
3
))
Volume of the room at which Indoor Unit of the least capacity is installed
!
WARNING
• Pipe to be vacuumed : gas pipe, liquid pipe
• If the refrigerant amount is not exact, it may not operate properly.
• If additionally bottled refrigerant amount is over 10%, condenser burst or insufficient indoor
unit performance may be caused.
• The total amount of refrigerant can be added up to 15%.
!
Refrigerant charging