TEST RUN
ENGLISH
Self-Diagnosis Function
Error Indicator
- This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
- Error mark is displayed on display window of indoor units and wired remote controller, and 7-seg-
ment LED of outdoor unit control board as shown in the table.
- If more than two troubles occur simultaneously, lower number of error code is first displayed.
- After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
1st,2nd,3rd LED of 7-segment indicates error number, 4th LED indicates unit number.
(* = 1:Master, 2:Slave 1, 3:Slave 2)
Ex)
* Refer to the DX-Venitilation manual for DX-Venitilation error code.
Display Title Cause of Error
Indoor unit related error
0 1 -
Air temperature sensor of indoor unit Air temperature sensor of indoor unit is open or short
0 2 -
Inlet pipe temperature sensor of indoor
unit
Inlet pipe temperature sensor of indoor unit is open or short
0 3 -
Communication error : wired remote
controller ÷ indoor unit
Failing to receive wired remote controller signal in indoor
unit PCB
0 4 -
Drain pump Malfunction of drain pump
0 5 -
Communication error : outdoor unit ÷
indoor unit
Failing to receive outdoor unit signal in indoor unit PCB
0 6 -
Outlet pipe temperature sensor of indoor
unit
Outlet pipe temperature sensor of indoor unit is open or
short
0 9 -
Indoor EEPROM Error
In case when the serial number marked on EEPROM of
Indoor unit is 0 or FFFFFF
1 0 -
Poor fan motor operation
Disconnecting the fan motor connector/Failure of indoor
fan motor lock
1 7 -
Inlet Air temperature sensor of FAU Air temperature sensor of indoor unit is open or short
Outdoor unit related error
2 1 *
Master Outdoor Unit Inverter Compressor
IPM Fault
Master Outdoor Unit Inverter Compressor Drive IPM Fault
2 2 *
Inverter Board Input Over Current(RMS) of
Master Outdoor Unit
Master Outdoor Unit Inverter Board Input Current excess
(RMS)
2 3 *
Master Outdoor Unit Inverter Com-
pressor DC link Low Voltage
DC charging is not performed at Master Outdoor
Unit after starting relay turn on.
2 4 *
Master Outdoor Unit High Pressure
Switch
System is turned off by Master Outdoor Unit
high pressure switch.
2 5 *
Master Outdoor Unit Input Voltage
High/ Low Voltage
Master Outdoor Unit input voltage is over 289V
or below 173V(ARUB***BTE4)
Master Outdoor Unit input voltage is over 506V
or below 414V(ARUB***DTE4)
2 6 *
Master Outdoor Unit Inverter Com-
pressor Start Failure
The First Start Failure by Master Outdoor Unit In-
verter Compressor Abnormality
Error No. of Compressor
Error No.
Error No. of Unit
Repeat