TEST RUN
ENGLISH
Display Title Cause of Error
Outdoor unit related error
6 0 *
Inverter PCB EEPROM Error of Master
Outdoor Unit
Access Error of Inverter PCB of Master Outdoor
Unit
6 2 *
Master Outdoor Unit Inverter Heatsink
High Temperature
System is turned off by Master Outdoor Unit In-
verter Heatsink High Temperature
6 5 *
Master Outdoor Unit Inverter Heatsink
Temperature Sensor Fault
Master Outdoor Unit Inverter Heatsink Temper-
ature Sensor open or short
6 7 *
Master Outdoor Unit Fan Lock Restriction of Master Outdoor Unit
7 1 *
Converter CT Sensor Error of Master
Outdoor Unit
Converter CT Sensor open or short of Master
Outdoor Unit
7 5 *
Master Outdoor Unit Fan CT Sensor
Error
Master Outdoor Unit Fan CT Sensor open or
short
7 6 *
Master Outdoor Unit Fan DC Link High
Voltage Error
Master Outdoor Unit Fan DC Link High Voltage
Error
7 7 *
Master Outdoor Unit Fan Over Current
Error
Master Outdoor Unit Fan Current is over 5A
7 9 *
Master Outdoor Unit Fan Start Failure
Error
Master Outdoor Unit Fan First Position Sensing
Failure
8 6 *
Master Outdoor Unit Main PCB EEP-
ROM Error
Communication Fail Between Master Outdoor
Unit Main MICOM and EEPROM or omitting
EEPROM
8 7 *
Master Outdoor Unit Fan PCB EEP-
ROM Error
Communication Fail Between Master Outdoor
Unit Fan MICOM and EEPROM or omitting
EEPROM
Loading ...