CLEARANCES
Installation clearances and protection of combustible surfaces shall comply with the
current local regulations eg. AG 601 (AS 5601) Gas Installations code.
Installation shall comply with the dimension in Fig. 1a bearing in mind that.
Overhead Clearances
In no case shall the clearances between the highest part of the cooker be less than
600 mm or for an overhead exhaust fan 750 mm. AII other downward facing com-
bustible surfaces less than 600 mm above the cooker surface shall be protected for the
full width of the cooking surface in accordance with the standards noted above. In no
case shall the clearance be less than 450 mm.
Rear and Side Clearances
Where the dimensions from the periphery of the nearest burner to any vertical com-
bustible surface is less than 200 mm the surface shall be protected in accordance with
the standards to a height of not less than 150 mm above the cooking surface for the
full width or depth of the cooking surface.
Where the dimensions from the periphery of the nearest burner to any horizontal com-
bustible surface is less than 200 mm, the horizontal surface shall be greater than
10 mm below the surface of the hob, or the horizontal surface requirement above.
Protection of combustible surfaces.
The standards above specify that where required protection shall ensure that the sur-
face temperature of the combustible surface does not exceed 65°C above room tem-
perature.
If the cooker is located on a pedestal it is necessary to provide safety mea-
sures to prevent falling out.