ON
OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
LED
Blinking →
MUZ-GL09/12/15/18NA
MUZ-GL09/12/15/18NAH
MUY-GL09/12/15/18NA
Inverter P.C. board
MUZ-GL24NA
MUZ-GL24NAH
MUY-GL24NA
LED
→
Blinking
No. Symptom LED indication
Abnormal point/
Condition
Condition Remedy
16
Outdoor unit
operates.
1-time blink
2.5 seconds OFF
Frequency drop by
current protection
MUZ-
GL09/12/15/18
MUY-
GL09/12/15/18
When the input current exceeds ap-
proximately 10.5A, compressor fre-
quency lowers.
The unit is normal, but check the
following.
•
Check if indoor lters are clogged.
•
Check if refrigerant is short.
•
Check if indoor/outdoor unit air
circulation is short cycled.
MUZ-GL24
MUY-GL24
Current from power outlet is nearing
breaker capacity.
17
3-time blink
2.5 seconds OFF
Frequency drop by
high pressure pro-
tection
Temperature of indoor coil thermistor exceeds 131 °F (55°C)
in HEAT mode, compressor frequency lowers.
Frequency drop by
defrosting in COOL
mode
Indoor coil thermistor reads 46°F (8°C) or less in COOL mode,
compressor frequency lowers.
18
4-time blink
2.5 seconds OFF
Frequency drop by
discharge tempera-
ture protection
Temperature of discharge temperature thermistor exceeds
232°F (111°C), compressor frequency lowers.
•
Check refrigerant circuit and refrig-
erant amount.
•
Refer to 10-5.
"Check of LEV".
•
Refer to 10-5.
"Check of outdoor
thermistors".
19
5-time blink
2.5 seconds OFF
Outside temperature
thermistor protec-
tion
When the outside temperature thermistor shorts or opens,
protective operation without that thermistors is performed.
•
Refer to 10-5.
Check of outdoor
thermistors.
20
7-time blink
2.5 seconds OFF
Low discharge tem-
perature protection
Temperature of discharge temperature thermistor has been
122°F (50°C) or less for 20 minutes.
•
Refer to 10-5.
"Check of LEV".
•
Check refrigerant circuit and refrig-
erant amount.
21
8-time blink
2.5 seconds OFF
MUZ-GL09/12/15/18
MUY-GL09/12/15/18
PAM protection
PAM: Pulse Ampli-
tude Modulation
The overcurrent ows into PFC (Power factor correction
:IC820) or the Bus-bar voltage reaches 394 V or more, PAM
stops and restarts.
This is not malfunction. PAM pro-
tection will be activated in the fol-
lowing cases:
1 Instantaneous power voltage
drop. (Short time power failure)
2 When the power supply voltage
is high.
MUZ-GL24
MUY-GL24
Zero cross detecting
circuit
Zero cross signal cannot be detected.
•
It occurs with following cases.
1 Instantaneous power voltage
drop. (Short time power failure)
2 Distortion of primary voltage
•
Refer to 10-5.
"Check of power
supply".
22
9-time blink
2.5 seconds OFF
Inverter check mode The connector of compressor is disconnected, inverter check
mode starts.
•
Check if the connector of the com-
pressor is correctly connected.
Refer to 10-5.
"How to check
inverter/compressor".
NOTE: 1. The location of LED is illustrated at the right gure. Refer to 10-6.1.
2. LED is lit during normal operation.
3. Blinking patterns of this mode dier from the ones of the failure recall mode.
The blinking frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the blinking frequency is “2”.
OBH733J