Set the refrigerant address using the DIP switch of the outdoor unit.
1 Wiring from the Remote Control
This wire is connected to TB5 (terminal board for remote controller) of the indoor
unit (non-polar).
2 When a Different Refrigerant System Grouping is Used.
Up to 16 refrigerant systems can be controlled as one group using the slim MA
remote controller.
Note:
In single refrigerant system (twin), there is no need of wiring
2
.
A Outdoor unit
B Indoor unit
C Master remote controller
D Subordinate remote controller
E Standard 1:1 (Refrigerant address = 00)
F
Simultaneous twin (Refrigerant address = 01)
G
Simultaneous twin (Refrigerant address = 02)
E SW 1 - 3 ~ 6
F SW 1 - 3 ~ 6
G SW 1 - 3 ~ 6
9. System control (Fig. 9-1)
Fig. 9-1
SW1
Function table
<SW1>
Function
Operation according to switch setting
ON OFF
SW1
function
settings
1 Compulsory
defrosting
Start Normal
2 Error history
clear
Clear Normal
3
4
5
6
Refrigerant
system ad-
dress setting
Settings for outdoor unit addresses
0 to 15
TB1
A GFAA E
B B B B B
D
C
TB1 TB1
TB4
TB5
TB4
TB5
TB4 TB4
TB5
TB4
1
1
2
ON
OFF
ON
OFF
ON
OFF
3 4 5 6
3 4 5 6
3 4 5 6
ON
OFF
2
10. Low ambient cooling
Precautions for low ambient cooling
If the outdoor temperature is 23 °F or lower during cooling operation, install an optional air guide to prevent wind from blowing into the outdoor unit.
Install the outdoor unit in a location where wind will not blow onto the back of the unit.
To prevent damage to the parts, be sure to install the unit, turn on the main power, and perform service in an environment where the ambient temperature is 0 °F or higher.
In order to protect the compressor and electrical components, do not turn off the circuit breaker if the unit is installed in an environment where the ambient temperature is 0
°F or lower.
It needs at least 12hr standby to operation in order to warm the electrical parts.