You can connect the RS-485 terminal with the RS-485 card reader,
connect the NC and COM terminal with the door lock, connect
the SENSOR terminal with the door contact, the BTN/GND
terminal with the exit buon, connect the alarm output and input
terminal with the alarm output/input devices, and connect the
Wiegand terminal with the Wiegand card reader or the access
controller.
If connect the WIEGAND terminal with the access controller, the
face recognion terminal can transmit the authencaon
informaon to the access controller and the access controller can
judge whether to open the door or not.
Note
●
If cable size is 18 AWG, you should use a 12 V power supply.
And the distance between the power supply and the device
should be no more than 20 m.
●
If the cable size is 15 AWG, you should use a 12 V power
supply. And the distance between the power supply and the
device should be no more than 30 m.
●
If the cable size is 12 AWG, you should use a 12 V power
supply. And the distance between the power supply and the
device should be no more than 40 m.
4.1 Terminal Descripon
The terminals contains power input, alarm input, alarm output,
RS-485, Wiegand output, and door lock.
The terminal's diagram is as follows:
Figure 4-1 Terminal Diagram
The descripons of the terminals are as follows: